The NDC3(GV、N)-40(11、11S)~95(11、11S) AC contactors have the AC 50/60Hz and the rated insulation voltage of 1000Vand are mainly used for the AC circuit with the rated voltage of 415A and the rated working current of 40~95A as well as the AC-3 utilization category for frequently starting & controlling AC motors.
2021 Quick Selection Guide »
| Parameter name | Description of the specific parameters | |||||||
| Specification | NDC3-40 | NDC3-50 | NDC3-65 | NDC3-80 | NDC3-95 | |||
| Number of poles | 3 | 3 | 3 | 3 | 3 | |||
|
Agreed thermal current of the free air Ith/A |
60 | 80 | 80 | 125 | 125 | |||
| Rated current(A) | AC-1 | 415V | 60 | 80 | 80 | 125 | 125 | |
| 690V | 60 | 80 | 80 | 125 | 125 | |||
| AC-3 | 415V | 40 | 50 | 65 | 80 | 95 | ||
| 690V | 32 | 35 | 39 | 48 | 48 | |||
| AC-4 | 415V | 33 | 41 | 55 | 66 | 79 | ||
| 690V | 21 | 21 | 21 | 40 | 40 | |||
|
Average resistance Per pole mΩ |
Ith 50Hz | 1.5 | 1.5 | 1.5 | 0.8 | 0.8 | ||
|
Power dissipation W per pole |
AC-3 | 2.4 | 3.7 | 6.3 | 5.1 | 7.2 | ||
| AC-1 | 5.4 | 9.6 | 9.6 | 12.5 | 12.5 | |||
| Rated working voltage(V) | AC220/230/240V,AC380/415V,AC660/690V | |||||||
| Insulation voltage Ui | 1000V | |||||||
| Impulse withstand voltage | 8kV | |||||||